Skip to main content
[image src=”2659″ alt=”” href=”” title=”” info_content=”” lightbox_caption=”” id=”image-product” class=”image-product” style=””]
[text_output]
Microprocessor temperature monitor system for electrical transformers with 2 inputs for PTC probes
[/text_output][gap size=”45px” id=”” class=”” style=””][text_output]
  • Two PTC inputs with fixed temperature level
    (see PTCK series sensors)
  • Possibility to connect up to six PTCK sensors in line for each channel (max. 1.5 Kohm for channel)
  • Interconnections among the relays contacts are shown in schema
  • Visualization correct working state
  • Visualization pre-alarm and alarm state
  • Intrinsic sure protection system with relays always on and signalling with switch off relays
  • Delay at power on (1 sec. about) for a direct connection with a shut down device
  • Assembly on rear panel by quick coupling with Din rail
  • Power supply (220 ÷ 240) Volt AC 50/60Hz
  • Tropicalization (optional)
[/text_output][gap size=”45px” id=”” class=”” style=””][vc_btn title=”MANUAL” style=”outline” shape=”round” color=”primary” i_icon_fontawesome=”fa fa-file-pdf-o” add_icon=”true” link=”url:https%3A%2F%2Fwww.diel-ed.it%2Fwp-content%2Fuploads%2F2018%2F12%2FMT-300-DIN-2018_1_2.pdf||target:%20_blank|”]
[text_output]
Technical features
[/text_output]
[text_output]

Dimensions

  • Standard box suitable for DIN rail 90x52X57 mm
  • Front panel 49×42 mm
  • Weight 0,2 Kg

Power Supply

  • Power supply (220 ÷ 240) Volt AC ± 10% 50/60Hz, absorption 2VA

Inputs

  • Two distinguished input channels for PTC sensors with possibility to connect max six sensors in serial connections on every branch
    (max 1.5 Kohm per branch)

Outputs

  • Output by relays with free contacts connected as per schema at the end of the manual.
[/text_output]
[text_output]

Characteristics

  • Self-extinguishable NORYL Box
  • Protection degree front panel in polycarbonate: IP30
  • Protection degree on terminal board side: IP20
  • Two 250V AC, 5A maximum relays contact (resistive load)
  • Dielectric strength between relays contacts and
    alimentation line 2,5KV for 60”
  • Working temperature of device from -40°C to 60°C
  • Max allowed dampness in the room 90% not condensing
  • Electrical connections with fast-polarised connectors
  • Technical manual in five languages (and more on request)
  • Construction in accordance with rules 
  • Tropicalization (optional)
[/text_output]
[image src=”2981″ alt=”” href=”” title=”” info_content=”” lightbox_caption=”” id=”” class=”” style=””]