Microprocessor temperature monitor system for resin, dry and oil transformers with 4 inputs for 3 wires PT100 probes.
- Control and showing temperature
- Control of fan systems
- Four independent PT100 inputs with three wires
- Four 250 Volt 10 A AC (resistive load) relays of outputs for the following functions: pre alarm state, alarm state, fault probe state, fan control with hysteresis
- Manual test relays to simulate or check the reliability of the contact
- Advanced programming menu: is allowed able, enable and set separately each single channel
- Permanent storing of programmed set of pre-alarm and alarm state, on, off fan and history values achieved
- Assembly on panel by simple fixing jaws
- Universal power supply (24 ÷ 240) Volt AC/DC 50/60Hz
- Protocol MODBUS – RTU communication (MT 200 S)
- Protocol MODBUS – RTU communication and galvanically insulated analogical output 4-20mA (MT 200 C)
- Protocol MODBUS – TCP, ETHERNET communication (MT 200 E)
- Tropicalization (optional)
Models
MT 200
Temperature controller device, 4 inputs PT100 probes, 4 relays
COD.: MT200LITE
MT 200 50121-5
Temperature controller device, 4 inputs PT100 probes, 4 relays according to EN 50121-5 rule
COD.: MT200L 50121-5
MT 200 S
Temperature controller device, 4 inputs PT100 probes, 4 relays, serial communication RS485 half duplex, MODBUS-RTU protocol
COD.: MT200LITE S
MT 200 C
Temperature controller device, 4 inputs PT100 probes,
4 relays, analogical communication 0-20 or 4-20 mA and serial communication RS485 half duplex, MODBUS-RTU protocol
COD.: MT200LITE C
MT 200 E
Temperature controller device, 4 inputs PT100 probes, 4 relays, ETHERNET communication, MODBUS-TCP protocol
COD.: MT200LITE E
Technical features
Dimensions
- Box 90x90x115 mm included terminal blocks
- Front panel 96×96 mm
- Weight 0,4 Kg
Power Supply
- Power supply (24 ÷ 240) Volt AC/DC ± 10% 50/60 Hz without polarity respect, absorption 4 VA
Inputs
- Four analogical inputs, temperature control and mapping with PT100 sensor at three wires inside range from -10°C to +200°C
Outputs
- Four relays 250V AC, 10 A max (resistive load), free switch contact
- RS485 Half Duplex protocol MODBUS-RTU (MT 200 S)
- RS485 Half Duplex protocol MODBUS-RTU, 4-20mA or 0-20mA galvanically isolated (MT 200 C)
- ETHERNET communication port, protocol MODBUS – TCP (MT 200 E)
Characteristics
- Self-extinguishable NORYL Box
- Protection degree front panel in polycarbonate: IP65 (IP66 on request)
- Protection degree of rear panel on terminal board side: IP20
- Display with light segments
- Visualisation of max temperature and the relevant channel in the automatic mode
- Alerts of pre-alarm, alarm, probes fault, fanning, manual function, historic highs
- System programming directly by frontal panel
- Possibility to select independently each channel
- Limit of alarm and pre-alarm settable in the range
(-9°C ÷ 199°C) - Precision ± 1% on full-scale ± 1 digit
- Cooling fan control on three or four channels
- Comparison of temperature for cooling fan between two different levels (L and H)
- Four selectable operating modes
- Detection of fault probes, maximum flexibility of managing and simplicity of programming, checking of validity of the insert data during programming phase
- Continuos storage of planned and reached values by each channel (limits and historic highs)
- Dielectric isolation: 2,5 KV AC for 60”
- Software configuration to control the environment temperature
- Resolution 1°C
- Working temperature of device from -40°C to 60°C
- Max allowed dampness in the room 90% not condensing
- Electrical connections with fast-polarised connectors
- Possibility of manual relays switch through menu test relays to simulate and check the reliability of contact
- Galvanically insulated output 4-20mA or 0-20mA
(MT200 C) - Maximum impedance allowed for current output
500 Ohm
Range 4-20mA (-10°C 4mA / +200°C 20mA)
Transformation formula (current in mA, temperature in °C):
lout = (T+10)/210*16 + 4
Range 0-20mA (-10°C 0mA / +200°C 20mA)
Transformation formula (current in mA, temperature in °C):
lout = (T+10)/210*20 (MT 200 C) - Certification for railway environment use according to EN-50121-5:2006 regulations (MT 200 EN50121-5)
- Configuration of IP address, port, subnet, gateway by browser web (MT 200 E)
- Technical manual in five languages
(and more on request) - Construction in accordance with rules
- Input filter for power supply in accordance with rules
- Tropicalization (optional)